User Instructions Low Temperature Freezers Model UNI/LT
9
OA1 Second relay configuration: ALr: alarm;
LHt: auxiliary; onF: always on;
dEF: do not select it!.; FAn: do not select it!.;
AoP Alarm relay polarity: it set if the alarm
relay is open or closed when an alarm hap-
pens. CL= the relay is closed; oP = the relay
is open
i1P Digital input polarity: oP: the digital input
is activated by opening the contact; CL:
the digital input is activated by closing the
contact.
i1F Digital input configuration:
EAL = external alarm: “EA message is dis-
played; bAL = serious alarm CA message is
displayed. PAL = pressure switch alarm, “CA
message is displayed; dor = door switch
function; dEF = activation of a defrost cycle;
LHt =switch on the second relay if oA1=LHt;
Htr = kind of action inversion (cooling – heat-
ing).
did: (0÷255 min)
with i1F= EAL or i1F = bAL digital input alarm
delay: delay between the detection of the
external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch func-
tion: time interval to
calculate the number of the pressure switch
activation.
nPS Pressure switch number: (0 ÷15) Number
of activation of the pressure switch, during
the “did” interval, before signalling the
alarm event (I2F= PAL). If the nPS activation
in the did time is reached, switch off and on
the instrument to restart normal regulation.
odc Compressor status when open door:
no, Fan = normal; CPr, F_C = Compressor
OFF
OTHER
PbC Type of probe: it allows to set the kind
of probe used by the instrument: PbC = PBC
probe, ntC = NTC probe.
• rEL Software release for internal use.
• Ptb Parameter table code: readable only.
DIGITAL INPUT
The free contact digital input is program-
mable in five different configurations by the
i1F parameter.
DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corre-
sponding relay output status through the
odc parameter:
no, Fan = normal (any change);
CPr, F_C = Compressor OFF;
Since the door is opened, after the delay
time set through parameter did, the door
alarm is enabled, the display shows the mes-
sage dA and the regulation restarts. The
alarm stops as soon as the external digital
input is disabled again. With the door open,
the high and low temperature alarms are
disabled.
GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the
unit will wait for did” time delay before
signalling the EAL alarm message. The
outputs status don’t change. The alarm
stops just after the digital input is de-acti-
vated.
SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit
will wait for did delay before signalling the
CA alarm message. The relay outputs are
switched OFF. The alarm will stop as soon as
the digital input is de-activated.
PRESSURE SWITCH (i1F = PAL)
If during the interval time set by did pa-
rameter, the pressure switch has reached
the number of activation of the nPS pa-
rameter, the CA pressure alarm message
will be displayed. The compressor and the
regulation are stopped. When the digital
input is ON the compressor is always OFF.
If the nPS activation in the did time is re-
ached, switch off and on the instrument
to restart normal regulation.
SWITCHING SECOND RELAY ON (i1F = LHt)
With oA1= LHt it switches on and off the
second relay.
START DEFROST (i1F = dFr)
It starts a defrost if there are the right condi-
tions. After the defrost is finished, the normal
regulation will restart only if the digital input
is disabled otherwise the instrument will wait
until the “MdF” safety time is expired.
INVERSION OF THE KIND OF ACTION: HEAT-
INGCOOLING (i1F = Htr)
This function allows to invert the regulation of
the controller: from cooling to heating and
viceversa.
Przeglądanie stron 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Komentarze do niniejszej Instrukcji

Brak uwag

Faber STIL30SS300B Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Dunstabzugshauben Faber STIL30SS300B.
Wir stellen 2 PDF-Handbücher Faber STIL30SS300B zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Handbuch, Spezifikationen


Faber STIL30SS300B Spezifikationen (2 Seiten)


Marke: Faber | Kategorie: Cooker hoods | Größe: 2.20 MB |

 

Inhaltsverzeichnis





Weitere Produkte und Handbücher für Dunstabzugshauben Faber

Modelle Dokumententyp
TEND30SS300-B Installationshandbuch    Faber TEND30SS300-B Installation Sheet, 32 Seiten
DIAMIS36SS Spezifikationsblatt   Faber DIAMIS36SS Spec Sheet/ Dimensions (PDF), 2 Seiten
STILIS36SS Spezifikationen   Faber STILIS36SS Specifications [de] , 2 Seiten
STIL36SS600B Spezifikationen   Faber STIL36SS600B Specifications, 2 Seiten
CRIS30SSH300 Bedienungsanleitung   Faber CRIS30SSH300 cristalspecSS, 3 Seiten
CRIS24SS300 Spezifikationsblatt   Faber CRIS24SS300 Spec Sheet, 2 Seiten
CYLNIS15SS Spezifikationsblatt   Faber CYLNIS15SS Spec Sheet/ Dimensions (PDF), 2 Seiten
MAES36SS Installationshandbuch    Faber MAES36SS Installation Instructions, 20 Seiten
DIAMIS36SS Installationshandbuch    Faber DIAMIS36SS Installation Instructions (PDF), 17 Seiten
VELV30SS Installationshandbuch    Faber VELV30SS Installation Instructions (PDF), 14 Seiten
MAES36SS Spezifikationen   Faber MAES36SS Specifications, 2 Seiten
INLX21SS600B Installationshandbuch   Faber INLX21SS600B Installation Instructions, 16 Seiten
DIAMIS36SS Spezifikationen   Faber DIAMIS36SS Specifications, 2 Seiten
LEVL30SS400 Spezifikationsblatt   Faber LEVL30SS400 Specifications Sheet, 2 Seiten
GLASIS36SS600B Installationshandbuch    Faber GLASIS36SS600B Installation Instructions [nl] , 40 Seiten
CRIS24SS300 Bedienerhandbuch    Faber CRIS24SS300 Instruction Guide, 16 Seiten
OSTR30SS400 Installationshandbuch    Faber OSTR30SS400 Installation Instructions, 40 Seiten
VELV30SS Spezifikationen   Faber VELV30SS Specifications [de] , 2 Seiten
STILIS36SS Installationshandbuch    Faber STILIS36SS Installation Instructions, 17 Seiten
INPL3019SSNB-B Spezifikationsblatt   Faber INPL3019SSNB-B Specifications Sheet, 2 Seiten